Updated:

Pre-Construction Design Specifications: Water Piping Sub-System Report

Exclusively available on Available only on IvyPanda® Made by Human No AI

Product design specification considerations

The product design specification development for the Water sub-system takes consideration of various factors (Daryll, 2008: 98). The factors are well illustrated in the diagram attached below;

Product design specification considerations

The diagram presumes that there is already a product conceptual design and hence focuses on deciding on of design shape, material selection, and selection of a process to make the design. An output of any design should clearly detail the way in which the product is made and its standard manufacturing/processing procedures (Singh, 2001: 67). The specification takes into account the manufacturer’s capability, materials relative performance, the behavior of the target market and functionality of the overall system (DETR, 2000).

Plumbing system decision matrix

Criteria
IdeaComplexity & ImplementationTemperature Accuracy * 2Thermal Capacitance * 1.5Total
Weight121.54.5
Design 14.006.504.5015.00
Design 23.009.506.3818.88
Design 32.004.004.5010.50
Design 42.254.503.7510.50

The criteria is described to encompass flexible PDS criteria but were more specific to plumbing systems. The criteria of complexity and implementation are related to the flexible PDS criteria of the system being powering set-up, repeatability of measurement, reduced temperature setup time, and progressive heating/cooling supply temperature (Belfast Engineering Institute, 2009). The criteria of temperature accuracy and thermal capacitance refer to high measurement repeatability and constant heating/cooling supply temperature. The thermal capacitance is a phrase used to describe the amount of energy that will be absorbed into (or from) plumbing parts between the temperature source and the puck.

Plumbing systems for a building water system is made up of pipes, fittings, and water tanks as appropriate (Frankel, 2005). The most common pipes used are either metallic or plastic pipes. Fittings are used in coupling of pipe lengths, corner turnings, branching of pipes, pipe size reduction or increment and in connecting the pipes to fixtures like tanks among others. Pipes are often customized to fit the purpose for which they are intended. They differ in diameter, material and make-up depending on the purpose for which they are intended. Indoor pipes are mostly made of copper and galvanized iron with diameters ranging from ½ inch, ¾ inch to 1 inch. Some water supply pipes are made from plastic materials. Ice makers, dispensers for hot water, water filters among others receive their water supply via plastic /flexible copper tubing of reduced diameter (Cummings, 2008). Fittings used are often made of brass or plastic. The double line orthographic drawing below describes the sample piping systems that is to be used in a house building. As seen the piping system is made up of pipes, flanges, connectors and valves.

sample piping
Figure 1: sample piping.

The single-line orthographic drawing below describes the water system for the building. Pipes with large diameters are used in the drain waste vent systems. They are normally 1.5 inches to 4 inches in diameter. Water is delivered into the home via the main pipe which is larger in diameter compared to the rest via a meter from the water-providing company( see figure 2). These pipes deliver the water to the main house tank(s) from where the water will be distributed to the house piping system.

Metering at the main pipe delivering water into the house main tank
Figure 2: Metering at the main pipe delivering water into the house main tank.

The diagram below describes the water system used for a building.

Design for building water system showing a system of pipes, valves, connectors and the tanks
Figure 3: Design for building water system showing a system of pipes, valves, connectors and the tanks.

The building water system design

The water tanks are located on top of the building and are placed at approximately 1.2 meters away from the edge of the building. The water pipes in this case are made of copper and are provided with Foam tubing with no sticky-strip type of insulation to reduce the effect of energy losses (Vennix et al., 1990). The thickness determines the level of insulation obtained. For instance, 3/8 inch walled insulation will conserve lesser heat as compared to 5/8 inch wall insulation (see diagram below).

Insulation material
Figure 4: Insulation material.

Two kinds of tanks are needed given their different function i.e. one handling hot water and another handling cold water.

Cost estimation

The estimated costs of materials to be used in building the system and the actual construction are summarized in the table below;

DescriptionUnit costNo. of unitsTotal cost
Cold water tank$ 120.001$120
Hot water tank$ 165.001$165
Pipes$ 1.5080$120
Valves$ 0.7515$11.25
Corner turnings$ 1.0010$10
Couplings$ 1.2012$14.4
Tools and equipment$ 200.001$200
Miscellaneous$ 150.001$150
Contingency costs$ 120.001$120
Total Cost910.65

Figure 5: Cost Estimation Table

Tanks design

Sample Tank Appearance And Insulation
Figure 6: Sample Tank Appearance And Insulation

The system is made up of two kinds of tanks. The first tanks carries cold treated water whiles the second one carries hot treated water. Standard insulation jackets are used in reducing the effect of heat losses from the hot water tank (see diagram below).

A range of materials exist for usage in water tanks (Randolph, 2010). These include plastic tanks, fiberglass, concrete tanks, welted/bolted steel tanks, and earthen tanks. In this case a plastic cold water tank is proposed from cold water and a ceramic lined steel tank for hot water. Plastic tank is preferred due its inability to react with any chemicals used in treating water or other present in water. The steel tank for hot water is lined with ceramic internally and covered with external jackets. The ceramic ensures not reactions between chemicals in water and the tank while at the same helping conserve heat alongside the insulation jackets.

Pipe’s selection

Basically two types of pipes are used in construction of the building’s water system. Cooper tubing’s are used in transmission of cold water across the house system. This is due to their inexpensive and durable characteristics.

Copper Tubing Sizes
Figure 7: Source: Copper Tube Handbook, the Copper Development Association, New York, USA, 2006

In residential buildings, type bearing medium thickness in comparison to the two is used. The material choice will there fore be type L cooper tubing’s (Sawah et al., 2009). Copper pipes are basically selected due its corrosion resistance activity and its longevity despite costing more than plastic. In supplying, hot water from the hot water tank to consumption, galvanized iron tubes will be used. The galvanized hot water pipes are used due to their ability to their high temperature resistance properties.

Sample Piping Assembly
Figure 8: Sample Piping Assembly to Be Used In Water System for the Building

The sample assembly design illustrates the assembly procedures to be employed in setting up of the system.

Screened Filter
Figure 9: Screened Filter

The screened filter is connected to the tank as shown.

Further illustration of fittings
Figure 10: Further illustration of fittings
Sample Copper Pipe, Corner Connectors and Connectors
Figure 11: Sample Copper Pipe, Corner Connectors and Connectors for the Water System

Water to be used

The water to be used in the pipes is treated water from supply companies. Such water contains chemicals such as chlorine and is also likely to have corrosive effect on the piping system and the storage tanks. It is on this basis that copper pipes were chosen due to their higher resistance to corrosion, longevity and reduced costs. The effect of water on pipes cannot be ignored as the effect of hot water and cold water may vary slightly. Hot water consumes a lot of energy if exposed to the environment and hence the need for insulation materials. This limits the energy loss.

Conclusion

The choice of design and materials to be used in the piping system is largely dependent on economic considerations, ability of the chosen materials to withstand the conditions of intended operations, and ease of assembly (Brian, 2006). Additionally, durability is taken into consideration. It is noted that corrosion is major cause of piping system failures long before they give back benefits. This is however catered for by choosing in materials selection. The overall design outcome is expected to not only offer an effective piping system but also to be aesthetically appealing to the intended users. Energy conservation is also critical to any manufacture. Noting that the water system will involve a hot system, measures to ensure minimal losses of energy are put in place. Insulation materials are provided to limit heat loss. In general, the earlier described considerations guide the course taken by the design.

References

Belfast Engineering Institute (2009). .

Brian, P. (2006). Choosing the best approach in assembly and manufacturing. Journal of Manufacturing processes, 45(4), 456-472.

Cummings, S.J. (2008). Australian water closet developments and their role in sustainable sanitation. Department of Industrial Design, University of Canberra, Australia.

Daryll, P. (2008). Product Design Specification: Making the right choices. New York: John Wiley and Sons.

DETR (2000). Building a better quality of life: A Strategy for more Sustainable Construction. Department of Environment, Transport & Regions, UK.

Frankel, M. (2005). Facility Piping Systems Handbook. London: McGraw Hill.

Randolph, J. (2010). Water delivery systems. Web.

Sawah, S. E. et al. (2009). Modeling water resource in the Australian Capital Territory: Knowledge elicitation for system dynamics model building. 18th World IMACS / MODSIM Congress, Cairns, Australia.

Singh, H. (2001). Materials selection processes. India: Prakatch.

Vennix, J. et al. (1990). “A structured approach to knowledge elicitation in conceptual model building.” System Dynamics Review, 6(2), pp.194-208.

More related papers Related Essay Examples
Cite This paper
You're welcome to use this sample in your assignment. Be sure to cite it correctly

Reference

IvyPanda. (2022, May 5). Pre-Construction Design Specifications: Water Piping Sub-System. https://ivypanda.com/essays/pre-construction-design-specifications-water-piping-sub-system/

Work Cited

"Pre-Construction Design Specifications: Water Piping Sub-System." IvyPanda, 5 May 2022, ivypanda.com/essays/pre-construction-design-specifications-water-piping-sub-system/.

References

IvyPanda. (2022) 'Pre-Construction Design Specifications: Water Piping Sub-System'. 5 May.

References

IvyPanda. 2022. "Pre-Construction Design Specifications: Water Piping Sub-System." May 5, 2022. https://ivypanda.com/essays/pre-construction-design-specifications-water-piping-sub-system/.

1. IvyPanda. "Pre-Construction Design Specifications: Water Piping Sub-System." May 5, 2022. https://ivypanda.com/essays/pre-construction-design-specifications-water-piping-sub-system/.


Bibliography


IvyPanda. "Pre-Construction Design Specifications: Water Piping Sub-System." May 5, 2022. https://ivypanda.com/essays/pre-construction-design-specifications-water-piping-sub-system/.

If, for any reason, you believe that this content should not be published on our website, please request its removal.
Updated:
This academic paper example has been carefully picked, checked and refined by our editorial team.
No AI was involved: only quilified experts contributed.
You are free to use it for the following purposes:
  • To find inspiration for your paper and overcome writer’s block
  • As a source of information (ensure proper referencing)
  • As a template for you assignment
1 / 1